T-series Split System Air Conditioner
INSTALLATION INTRUCTIONS
• T25-R410 2.7kWSplitSystem
• T35-R410 3.6kWSplitSystem
• T50-R410 5.4kWSplitSystem
• T70-R410 7.5kWSplitSystem
• T70-R410i 7.5kWSplitSystemInverter
Seitenansicht 0
1 2 3 4 5 6 ... 14 15

Inhaltsverzeichnis

Seite 1

www.ayre.com.auT-series Split System Air ConditionerINSTALLATION INTRUCTIONS• T25-R410 2.7kWSplitSystem• T35-R410 3.6kWSplitSystem• T50-R410

Seite 2 - 2. Accessories

CAUTIONThe power cord connected to the indoor unit should becomplied with the following specifications(Type H05VV-F(Indoor), H07RN-F(Outdoor) approved

Seite 3 - 3. Split type installation

3.6.2 Connect the cable to the outdoor unitA. Remove the control cover from the unit by loosen-ing the screw.Connect the wires to the terminals on the

Seite 4 - 3.4 Drill a hole in the wall

3.7.2 Form the pipingA. Form the piping by wrapping the connecting portionof the indoor unit with insulation material and secureit with two kinds of v

Seite 5 - E. Check

3.8 Air purging3.8.1 Air purgingAir and moisture remaining in the refrigerant systemhave undesirable effects as indicated below.1) Pressure in the sys

Seite 6 - For right rear piping

C. Evacuation• Connect the charge hose end described in the preced-ing steps to the vacuum pump to evacuate the tubingand indoor unit.Confirm the &quo

Seite 7 - For left rear piping

B. Settlement of outdoor unit1) Anchor the outdoor unit with a bolt and nuttightly and horizontally on a concrete or rigid mount.2) When installing on

Seite 8 - Indoor unit

Screw driver Hand drill Ruler, knife Gas leak detector& soup waterThermometer Hex. wrench(Large side: 4mm, 5mm)Assembly,disassmblyIndoor installat

Seite 9 - 3.6kW, 5.4kW

2.7kW 3/8"1/4"3 or 5 5 3.6kW 1/2"1/4 3.5 or 5 5.4kW 1/4" 4.5 7.5kW

Seite 10 - ❒ 7.5kW Model

3.3 How to fix installation plateThe wall you select should be strong and solid enough toprevent vibration3.3.1 Mount the installation plate on the wa

Seite 11

3.5.1 Flaring workMain cause for gas leakage is due to defect in flaringwork. Carry out correct flaring work in the followingprocedure.A. Cut the pipe

Seite 12 - Downward slope

3.5.2 Connection of piping--Indoor1) Preparing the indoor unit's piping and drain hose forinstallation through the wall.2) Remove the plastic tub

Seite 13 - B. Leak test

F. Wrap the insulation material around the connectingportion.• Overlap the connection pipe insulation material and theindoor unit pipe insulation mate

Seite 14 - D. Finishing the job

C. Insert the connecting cable into the indoor unit.1) Don't connect the cable to the indoor unit.2) Make a small loop with the cable for easy co

Seite 15 - A. Prepare remote control

3.5.3 Connection of the pipes-OutdoorA. Align the center of the pipings and sufficiently tightenthe flare nut by hand.B. Finally, tighten the flare nu